kVA, kW, kvar and power factor
Why does the bill count demand in kVA, and what does power factor change?
Active power (kW) does useful work. Reactive power (kvar) builds magnetic and electric fields in motors, transformers and similar equipment. Apparent power (kVA) is the combination the network has to carry.
Power factor is kW divided by kVA. At a power factor of 1, kVA equals kW. Below 1, the network carries more kVA than the kW used.
Eskom measures maximum demand in kVA, so NMD, utilised capacity and the R/kVA charges built on them all rise when power factor falls.
Several tariffs add a reactive energy charge, in c/kvarh, on reactive energy above 30% of the kWh, which corresponds to a power factor of 0.96 or less. It applies only in the high-demand season. Megaflex measures it per half-hour in peak and standard periods; Miniflex and Ruraflex use billing-period totals.
Questions
The charge applies to reactive energy above 30% of kWh, which the schedule equates to a power factor of 0.96 or less.